首页|期刊导航|云南水力发电|某光伏电站35 kV接地变兼站用变断路器跳闸处理及分析

某光伏电站35 kV接地变兼站用变断路器跳闸处理及分析

蔡福禄

云南水力发电2024,Vol.40Issue(6):62-64,3.
云南水力发电2024,Vol.40Issue(6):62-64,3.DOI:10.3969/j.issn.1006-3951.2024.06.022

某光伏电站35 kV接地变兼站用变断路器跳闸处理及分析

Handling and Analysis of Tripping of 35 kV Grounding Transformer and Station Transformer Circuit Breaker in a Photovoltaic Power Station

蔡福禄1

作者信息

  • 1. 华电云南发电有限公司绿水河发电厂,云南 个旧 661014
  • 折叠

摘要

Abstract

Grounding transformer and station transformer are commonly used primary equipment in the power system.The main function of a grounding transformer is to artificially create a neutral point for connecting the grounding resistance.When a grounding fault occurs in the system,it can effectively present high impedance to positive and negative sequence currents,while presenting low impedance to zero sequence currents,ensuring reliable operation of grounding protection.The grounding transformer has the characteristics of long time and short time overload.It may remain idle for a long time,but in certain specific situations,such as system failures,it needs to be able to withstand short-term overloads to ensure system stability and safety.However,during use,various faults may occur in the grounding transformer and station transformer,affecting the normal operation of the power system.This paper proposes corresponding solutions by analyzing the handling and causes of faults in grounding transformers and station transformers in photovoltaic power plants.The aim is to exchange information on the maintenance and fault handling of grounding transformers and station transformers in photovoltaic power plants,and improve the level of on-site equipment operation and maintenance.

关键词

接地变兼站用变/断路器跳闸/故障处理/原因分析

Key words

grounding transformer and station transformer/circuit breaker tripped/fault handling/cause analysis

分类

信息技术与安全科学

引用本文复制引用

蔡福禄..某光伏电站35 kV接地变兼站用变断路器跳闸处理及分析[J].云南水力发电,2024,40(6):62-64,3.

云南水力发电

1006-3951

访问量0
|
下载量0
段落导航相关论文