|国家科技期刊平台
首页|期刊导航|电力系统保护与控制|大规模风电接入场景下的失步振荡中心定位方法

大规模风电接入场景下的失步振荡中心定位方法OA北大核心CSTPCD

Out-of-step oscillation center location method in a large-scale wind power integration scenario

中文摘要英文摘要

振荡中心的准确定位是失步保护正确动作的基础,大规模风电并网导致系统阻抗参数发生变化,使得传统基于阻抗轨迹的失步定位方法的适应性严重下降.针对该问题,提出基于节点频差的失步振荡中心定位方法.首先分析大规模风电并网对系统总阻抗的影响.进一步根据发电机功角,计算其曼哈顿距离相似度并构建启动判据.最后,通过移动平均法对广域测量频率进行平滑处理,提出基于节点频差的失步振荡中心定位方法.仿真验证表明,所提基于节点频差的失步振荡中心定位方法受噪声影响较小,不受风电渗透率的影响,能够准确定位失步振荡中心位置.

The accurate positioning of the oscillation center is the basis for correct action in out-of-step protection.Large-scale wind power integration causes system impedance parameters to change,resulting in a serious deterioration in the adaptability of the traditional out-of-step positioning method based on the impedance trajectory.To tackle this problem,an out-of-step oscillation center location method based on bus frequency is proposed.First,the influence of large-scale wind power integration on the total impedance of the system is analyzed.Further,from the power angle of the generator,the Manhattan distance similarity is calculated and a start-up criterion is constructed.Finally,the moving average method is used to smooth the wide-area measurement frequency,and an out-of-step oscillation center location method based on node frequency difference is proposed.Simulation results show that the proposed method is less affected by noise and is not affected by wind power penetration rate,and can accurately locate the out-of-step oscillation center.

李振兴;崔丹阳;胡聪;朱益;翁汉琍

新能源微电网湖北省协同创新中心(三峡大学),湖北 宜昌 443002

双馈风机风电渗透率等效阻抗同步机组失步节点电压频差振荡中心定位

double-fed induction generatorwind power penetration rateequivalent impedancesynchronization unit out-of-stepnode voltage frequency differenceoscillation center positioning

《电力系统保护与控制》 2024 (014)

1-12 / 12

This work is supported by the National Natural Science Foundation of China(No.52077120).国家自然科学基金项目资助(52077120)

10.19783/j.cnki.pspc.231334

评论