| 注册
首页|期刊导航|电力工程技术|基于零序导纳幅值比的同母两回线异相接地复故障选线方法

基于零序导纳幅值比的同母两回线异相接地复故障选线方法

韩捷 刘智勇 周歧林 童锐 凌毓畅 梁国开

电力工程技术2024,Vol.43Issue(4):253-261,9.
电力工程技术2024,Vol.43Issue(4):253-261,9.DOI:10.12158/j.2096-3203.2024.04.027

基于零序导纳幅值比的同母两回线异相接地复故障选线方法

Fault line selection method for earth faults occurred in different phases of two feeders connected to the same bus based on the ratio of zero-sequence admittance amplitude

韩捷 1刘智勇 1周歧林 1童锐 1凌毓畅 1梁国开1

作者信息

  • 1. 广东电网有限责任公司广州供电局,广东广州 510620
  • 折叠

摘要

Abstract

When the earth faults occur in different phases of two feeders connected to the same bus in the resonant grounding system,the conventional fault line selection devices are inaccurate.To address the difficulties of fault line selection in the earth faults that occurred in different phases of two feeders connected to the same busbar for resonant grounding system,the line zero-sequence admittance is calculated by the zero-sequence current at the first end of the line and the zero-sequence voltage of the bus.The analysis of the fault characteristics indicates that,the zero-sequence admittance amplitude in faulty lines is larger than that in the non-faulty line,and this characteristic also appears in the high-impedance grounding faults.Based on the ratio of zero-sequence admittance amplitude,a fault line selection method for earth faults occurring in different phases of two feeders connected to the same bus in a resonant grounding system is proposed.The difference in zero-sequence admittance amplitude between fault and non-fault lines is used to establish a line selection criterion,which allows all fault lines to be selected.The results simulated by PSCAD confirmed that the proposed method works effectively,with high accurary.This method is not affected by the fault location and the compensation degree of the arc suppression coil,and it can also withstand high fault resistances.

关键词

消弧线圈接地系统/同母两回线故障/异相接地/零序导纳/幅值比/故障选线

Key words

resonant grounding system/faults of two feeders connected to the same bus/earth faults occurred in different phases/zero-sequence admittance/the ratio of amplitude/fault line selection

分类

信息技术与安全科学

引用本文复制引用

韩捷,刘智勇,周歧林,童锐,凌毓畅,梁国开..基于零序导纳幅值比的同母两回线异相接地复故障选线方法[J].电力工程技术,2024,43(4):253-261,9.

基金项目

本文得到广州供电局有限公司科技项目(GZHKJXM20200081)资助,谨此致谢! (GZHKJXM20200081)

电力工程技术

OA北大核心CSTPCD

2096-3203

访问量5
|
下载量0
段落导航相关论文