| 注册
首页|期刊导航|电力勘测设计|某核电厂变压器零差保护跳闸案例分析

某核电厂变压器零差保护跳闸案例分析

陆建莺 王丽

电力勘测设计Issue(z1):32-37,6.
电力勘测设计Issue(z1):32-37,6.DOI:10.13500/j.dlkcsj.issn1671-9913.2024.S1.006

某核电厂变压器零差保护跳闸案例分析

Case Analysis of Transformer Zero-Sequence Differential Protection in NPP

陆建莺 1王丽1

作者信息

  • 1. 国核电力规划设计研究院有限公司,北京 100095
  • 折叠

摘要

Abstract

Zero-sequence differential protection of transformer is the main protection principle reflecting the single-phase grounding short circuit fault of transformer,which is applied cautiously.Starting from a case of zero difference protection tripping on the low-voltage side of a backup transformer in a nuclear power plant,by examining the recorded waveform and action timing of the fault recording device at the time of the event,checking the real-time status of the on-site equipment,analyzing the zero sequence current values before and after the protection tripping,and calculating the set value of the on-site protection,considering the impact of the starting mode of the medium voltage high-power motor on the unbalanced current of the circuit,it is analyzed that the protection action in this case is related to the starting mode of the high-power motor and the set value control logic of the transformer zero difference protection.With comparing with several other principles of zero-sequence differential protections,problems which need to be attention in the application of transformer zero-sequence differential protection are put forward.

关键词

零序差动保护/零序电流/制动特性

Key words

zero-sequence differential protection/zero-sequence current/braking characteristics

分类

动力与电气工程

引用本文复制引用

陆建莺,王丽..某核电厂变压器零差保护跳闸案例分析[J].电力勘测设计,2024,(z1):32-37,6.

电力勘测设计

1671-9913

访问量0
|
下载量0
段落导航相关论文