| 注册
首页|期刊导航|电力系统自动化|大扰动下计及风电场低电压穿越恢复差异的频率响应估计方法

大扰动下计及风电场低电压穿越恢复差异的频率响应估计方法

程昊 吕亚洲 李威 刘福锁 赖业宁 张宇栋

电力系统自动化2024,Vol.48Issue(16):68-78,11.
电力系统自动化2024,Vol.48Issue(16):68-78,11.DOI:10.7500/AEPS20230914005

大扰动下计及风电场低电压穿越恢复差异的频率响应估计方法

Frequency Response Estimation Method Considering Low Voltage Ride-through Recovery Difference of Wind Farms Under Large Disturbance

程昊 1吕亚洲 1李威 1刘福锁 1赖业宁 1张宇栋2

作者信息

  • 1. 国电南瑞南京控制系统有限公司,江苏省南京市 211106
  • 2. 国家电网有限公司西南分部,四川省成都市 610041
  • 折叠

摘要

Abstract

With the increasing penetration rate of the wind power,multiple wind farms entering into the low voltage ride-through(LVRT)at the same time will bring significant impacts to the power system,resulting in temporary drop in active power output,rapid drop in power grid frequency and even the risk of triggering under-frequency load shedding.It is necessary to quickly estimate the frequency curve of the power grid under the temporary power disturbances to develop corresponding control measures.However,due to the difference in power recovery within wind farms,LVRT curves present different shapes.If this impact is ignored,there will be significant estimation errors in the frequency response curve,and traditional time-domain simulation based on detailed model has low efficiency.Hence,a disturbance power analysis method considering LVRT recovery difference of wind farms is proposed.The active power disturbances caused by single-unit wind turbine at each stage of LVRT are described by segment functions,and the total temporary disturbance power of the system is accurately estimated based on energy conservation principle.Considering the frequency regulation characteristics of the wind farm and the virtual inertia effect,an optimized model for system frequency response suitable for power girds with high-proportion renewable energy is proposed.The differental evolution algorithm is used to identify the parameters of the system transfer function based on actual data,and then the frequency response trajectory is fitted.The applicability and reliability of the proposed method in different scenarios are verified by the simulation of IEEE 39-bus system and simplified system for actual power grid.

关键词

低电压穿越/扰动功率/能量守恒/参数辨识/频率响应估计

Key words

low voltage ride-through/disturbance power/energy conservation/parameter identification/frequency response estimation

引用本文复制引用

程昊,吕亚洲,李威,刘福锁,赖业宁,张宇栋..大扰动下计及风电场低电压穿越恢复差异的频率响应估计方法[J].电力系统自动化,2024,48(16):68-78,11.

基金项目

国家电网公司西南分部科技项目(SGSW0000DKJS2310035) (SGSW0000DKJS2310035)

已申请国家发明专利(申请号:202410212546.7). This work is supported by Southwest Branch of State Grid Corporation of China(No.SGSW0000DKJS2310035). (申请号:202410212546.7)

电力系统自动化

OA北大核心CSTPCD

1000-1026

访问量0
|
下载量0
段落导航相关论文