| 注册
首页|期刊导航|流体机械|双逆流式露点间接蒸发冷却器的性能试验研究

双逆流式露点间接蒸发冷却器的性能试验研究

蒋苏贤 黄翔 褚俊杰 代聪 梁凯 赵娅舒

流体机械2024,Vol.52Issue(9):8-15,8.
流体机械2024,Vol.52Issue(9):8-15,8.DOI:10.3969/j.issn.1005-0329.2024.09.002

双逆流式露点间接蒸发冷却器的性能试验研究

Experimental study on the performance of a double countercurrent dew-point indirect evaporative cooler

蒋苏贤 1黄翔 1褚俊杰 1代聪 1梁凯 1赵娅舒1

作者信息

  • 1. 西安工程大学 城市规划与市政工程学院,西安 710048
  • 折叠

摘要

Abstract

In order to use evaporative coolers in residential buildings to achieve a greater cooling temperature difference and reduce the size of the dew point core,a double countercurrent dew point indirect cooler was proposed,which combines double countercurrent design and efficient wet channel material.In the double enthalpy difference test room,by using dry bulb temperature of 35℃and wet bulb temperature of 25.8℃as the example,the cooling efficiency and cooling capacity,etc.of this cooler were analyzed.The results show that in the medium-humidity region,the secondary/primary air volume ratio is 0.9.When the spraying method of 15 s stop for 60 s is used,the wet bulb efficiency of the cooler reaches 104%,the dew point efficiency reaches 79%,he cooling capacity reaches 1.76 kW,and the highest COP is 7.5,which can meet the requirements of the indoor air supply temperature of 26~28℃and the energy consumption reduction in residential buildings.The study can provide a reference for the design of dew point air conditioners for residential buildings.

关键词

住宅建筑/双逆流式/露点间接蒸发冷却器/湿通道材料/制冷量

Key words

residential building/double countercurrent/dew-point indirect evaporative cooler/wet channel material/refrigerating capacity

分类

机械制造

引用本文复制引用

蒋苏贤,黄翔,褚俊杰,代聪,梁凯,赵娅舒..双逆流式露点间接蒸发冷却器的性能试验研究[J].流体机械,2024,52(9):8-15,8.

基金项目

国家自然科学基金项目(51676145) (51676145)

流体机械

OA北大核心CSTPCD

1005-0329

访问量0
|
下载量0
段落导航相关论文