| 注册
首页|期刊导航|西南交通大学学报|不同直流拓扑和敷设环境下35 kV交流XLPE电缆直流载流量分析

不同直流拓扑和敷设环境下35 kV交流XLPE电缆直流载流量分析

张添胤 王启隆 王新 金泱 杨敏 陈向荣

西南交通大学学报2024,Vol.59Issue(6):1285-1293,1304,10.
西南交通大学学报2024,Vol.59Issue(6):1285-1293,1304,10.DOI:10.3969/j.issn.0258-2724.20220704

不同直流拓扑和敷设环境下35 kV交流XLPE电缆直流载流量分析

Direct Current Ampacity of 35 kV Alternating Current Cross-Linked Polyethylene Cables Under Various Direct Current Topologies and Laying Environments

张添胤 1王启隆 1王新 2金泱 2杨敏 2陈向荣3

作者信息

  • 1. 浙江大学电气工程学院,浙江 杭州 310027||浙江大学杭州国际科创中心,浙江 杭州 311200
  • 2. 浙江浙能技术研究院有限公司浙江省火力发电高效节能与污染物控制技术研究重点实验室,浙江 杭州 311121
  • 3. 浙江大学电气工程学院,浙江 杭州 310027||浙江大学杭州国际科创中心,浙江 杭州 311200||浙江大学浙江省宽禁带功率半导体材料与器件重点实验室,浙江 杭州 311200||浙江大学先进电气国际研究中心,浙江海宁 314400
  • 折叠

摘要

Abstract

Converting alternating current(AC)cables into direct current(DC)operation is of great significance to achieve new energy generation connected to the grid and increase power supply capacity.A 35 kV AC cross-linked polyethylene(XLPE)cable was taken as the research object,and temperature field simulation of the three-core AC cable was carried out through the finite element method under three kinds of DC topologies:three-wire bipole,monopole,and bipole.At the same time,common influencing factors in the distribution network were considered,such as distance from hot water pipes,cable cluster laying,and current imbalance,so as to explore the influence of these factors on the ampacity of the cable when the AC cable was changed to the DC operation.The results show that under the same operating temperature,the 35 kV AC XLPE cable has the smallest ampacity when operating under the monopolar DC topology and the largest ampacity under the three-wire bipolar DC topology.When the horizontal distance between AC cable and urban water supply pipes is 2.0 m,and the vertical distance is 0.5 m,the ampacity of cables operating under the above kinds of DC topologies is reduced by about 3.0%.The maximum ampacity can be increased by 90 A as the asynchronous peak value is loaded when the cable cluster is laid.The cable ampacity increases first and then decreases with increasing current imbalance,and it reaches the maximum value when the current imbalance is 0.The research results can provide some reference for converting 35 kV AC XLPE cables into DC operation.

关键词

XLPE电缆/直流拓扑/敷设环境/直流载流量

Key words

XLPE cables/DC topologies/laying environment/DC ampacity

分类

信息技术与安全科学

引用本文复制引用

张添胤,王启隆,王新,金泱,杨敏,陈向荣..不同直流拓扑和敷设环境下35 kV交流XLPE电缆直流载流量分析[J].西南交通大学学报,2024,59(6):1285-1293,1304,10.

基金项目

浙江浙能技术研究院有限公司科技项目(JSYJY-SCFW-2022-009) (JSYJY-SCFW-2022-009)