建筑防潮设备对埋地钢质燃气管道的腐蚀风险

陈志光 吴聪 张静思 秦朝葵

煤气与热力2024,Vol.44Issue(12):59-66,8.
煤气与热力2024,Vol.44Issue(12):59-66,8.

建筑防潮设备对埋地钢质燃气管道的腐蚀风险

Corrosion Risk of Grounding Current of Building Moisture-proof Equipment to Buried Steel Gas Pipelines

陈志光 1吴聪 1张静思 1秦朝葵1

作者信息

  • 1. 同济大学机械与能源工程学院,上海 201804
  • 折叠

摘要

Abstract

The influence of ground current of building moisture-proof equipment on corrosion of bur-ied steel gas pipelines was studied by measuring the pipe-to-soil potential of buried steel gas pipelines,the ground potential of building metals and the soil surface potential gradient in nearby areas.The main source of stray current in soil is the grounding current of building moisture-proof equipment.The operation of building moisture-proof equipment generates a pulse current with an interference frequency of 1 Hz in the surround-ing soil of the building.The farther away from the cathode rod of the building moisture-proof equipment,the smaller the interference current in the soil.When one building moisture-proof equipment is turned on,the soil surface potential gradient drops to an acceptable range when the distance from the cathode rod of the building moisture-proof equipment is more than 30 me-ters.The change in the number of building moisture-proof equipment turned on can cause a change in the direction of current flow in the soil,thereby affecting the corrosion of building metals and buried steel gas pipelines.After the building moisture-proof equipment is turned on,the pipe-to-soil potential and the ground potential of building metals increase with the increase in the number of building moisture-proof equipment turned on,which increases the probability of corrosion occurring.

关键词

建筑防潮设备/接地电流/腐蚀/钢质管道/土壤表面电位梯度

Key words

grounding current of building mois-ture-proof equipment/corrosion/steel pipeline/soil sur-face potential gradient

分类

建筑与水利

引用本文复制引用

陈志光,吴聪,张静思,秦朝葵..建筑防潮设备对埋地钢质燃气管道的腐蚀风险[J].煤气与热力,2024,44(12):59-66,8.

煤气与热力

1000-4416

访问量0
|
下载量0
段落导航相关论文