基于暂态零序导纳值的谐振接地系统单相接地故障选线方法OA北大核心CSTPCD
Single-Phase Grounding Fault Line Selection Method for Resonant Grounding System Based on Transient Zero-Sequence Admittance Value
谐振接地系统削弱了故障线路和非故障线路的零序特征差异,为此提出了一种基于暂态零序导纳值的谐振接地系统选线方法.首先从理论上推导了单相接地故障下故障线路和非故障线路的暂态零序导纳公式,比较了两者的特征差异.在此基础上,构建了基于暂态零序导纳最大均值指标的单相接地故障选线方法.最后,基于PSCAD/EMTDC软件对所提方法的性能进行了全面的验证和测试.结果表明,所提方法具有耐受过渡电阻能力强的优势.仅需计算故障后半个工频周期内的暂态零序导纳,计算量小、速度快、易于实现.同时,在噪声干扰、电流互感器反接、网络拓扑结构变化、线路参数变化、采样频率变化等干扰因素下仍有较高的选线准确度.
The zero-sequence characteristic difference between faulty line and healthy line is weakened by resonant grounding system,so a line selection method based on transient zero-sequence admittance is proposed in this paper.Firstly,the transient zero-sequence admittance formulas of faulty line and healthy line under single-phase grounding fault are deduced theoretically,and the characteristic differences between them are compared.On this basis,a single-phase grounding fault line selection method based on the maximum mean value index of transient zero-sequence admittance is constructed.Finally,based on PSCAD/EMTDC software,the performances of the proposed method are verified and tested comprehensively.The results show that proposed method has the advantage of strong resistance tolerance to the transition resistance.Only the transient zero-sequence admittance in half power frequency cycle after the fault needs to be calculated,so the calculation load is small,the speed is fast and the implementation is easy.At the same time,the line selection accuracy is still high under the interference factors such as noise interference,current transformer reverse connection,the changes in network topology,line parameters and sampling frequency.
吴江雄;郑茂然;王欣;李海锋;罗会洪
广西电网有限责任公司桂林供电局,广西 桂林 541002中国南方电网电力调度控制中心,广州 510663华南理工大学电力学院,广州 510640华南理工大学电力学院,广州 510640中国南方电网电力调度控制中心,广州 510663
动力与电气工程
单相接地故障故障选线暂态零序导纳谐振接地系统
single-phase grounding faultfault line selectiontransient zero-sequence admittanceresonant grounding system
《南方电网技术》 2024 (11)
58-66,9
国家自然科学基金资助项目(51977080)广东省基础与应用基础研究基金项目(2023A1515011035)广西电网有限责任公司科技项目(GXKJXM20222111). Supported by the National Natural Science Foundation of China(51977080)the Basic and Applied Basic Research Fund Project of Guangdong Province(2023A1515011035)the Science and Technology Project of Guangxi Power Grid Co.,Ltd.(GXKJXM20222111).
评论