电瓷避雷器Issue(1):43-49,60,8.DOI:10.16188/j.isa.1003-8337.2025.01.006
有关华北风电集送系统中500 kV避雷器短时工频过电压试验的探讨
Short-Time Power Frequency Overvoltage Test of 500 kV Arrester in North China Centralized Wind Power Transmission System
摘要
Abstract
The performance of arrester to withstand short-time power frequency overvoltage affects the output capacity of wind power in North China.The author analyzes the characteristics of short-time pow-er frequency overvoltage of wind power gathering and transmission system in North China,and discusses the applicability of short-time overvoltage test procedures,the selection of test overvoltage multiples,the capacity of test equipment and other key issues related to test verification.Taking a 500 kV lightning ar-rester as an example,the short-time power frequency overvoltage test is conducted to verify the reliabili-ty of the lightning arrester,which provides an idea for the reliability verification method of lightning ar-rester in this system.关键词
短时工频过电压/风电集中送出式/避雷器Key words
short-time power frequency overvoltage/centralized wind power transmission system/arrester引用本文复制引用
王聪,王晨星,牛晓民,王茂海,彭珑,刘羿辰,刘慧林..有关华北风电集送系统中500 kV避雷器短时工频过电压试验的探讨[J].电瓷避雷器,2025,(1):43-49,60,8.基金项目
国家电网公司华北分部科技项目(新能源集中送出系统中基于避雷器TOV耐受特性的暂态过电压运行策略研究编号:1100/2022-02001B)Project supported by Science and Technology Project of State Grid Corporation of China North China Branch(Research on Transient Overvoltage Operation Strategy Based on TOV Tolerance Characteristics of Surge Arresters in New Energy Centralized Transmission Sys-tems)Number 11002022-02001B) (新能源集中送出系统中基于避雷器TOV耐受特性的暂态过电压运行策略研究编号:1100/2022-02001B)