电力勘测设计Issue(2):79-84,6.DOI:10.13500/j.dlkcsj.issn1671-9913.2025.02.014
1000MW机组自然通风直接空冷系统的应用研究
Application Research of Natural Ventilation Direct Air Cooling System for 1 000 MW Unit
汪正明 1梁琳达 1储剑锋1
作者信息
- 1. 中国电力工程顾问集团华东电力设计院有限公司,上海 200063
- 折叠
摘要
Abstract
Taking a 2×1 000 MW unit in northern China as an example,the basic configuration parameters of the natural ventilation direct air cooling system and the surface condensing indirect air cooling system are given,and the technical and economic comparison of the two air cooling systems is made.The results show that:in the technically,the natural ventilation direct air cooling system has a lower operating back pressure when the temperature is high.In the economically,the initial investment of natural ventilation direct air cooling is high,but the annual operating cost(including coal consumption)is low,and it has a good payback period.Finally,combined with the characteristics of natural ventilation direct air cooling system and the winter operation experience of the operation units,the effective measures for antifreeze and reducing the subcooling degree of condensate of natural ventilation direct air cooling system are given.关键词
自然通风直接空冷系统/运行背压/防冻/过冷度/投资回收年限Key words
natural ventilation direct air cooling system/operating back pressure/antifreeze/subcooling/payback period of investment分类
信息技术与安全科学引用本文复制引用
汪正明,梁琳达,储剑锋..1000MW机组自然通风直接空冷系统的应用研究[J].电力勘测设计,2025,(2):79-84,6.