Through the analysis of excitation waveform recordings and synchronous phasor measurement unit(PMU)data at Longtan Power Plant,this study identifies the root causes of significant voltage fluctuations at the facility.To address the limitations of conventional power system stabilizer(PSS)parameter tuning methods,we propose an optimized PSS parameter tuning approach incorporating small DC-blocking time constants that effectively suppresses system voltage fluctuations.Utilizing multiple validation methodologies including large-grid time-domain simulations,hardware-in-the-loop(HIL)closed-loop simulations with actual excitation regulators,and field tests on Units 3 and 4 of Longtan Power Plant,a comprehensive comparative evaluation was conducted between conventional PSS parameters and the proposed tuning scheme.The results demonstrate that the optimized PSS parameter configuration not only maintains equivalent damping performance for local and inter-area oscillations compared with original settings,but also achieves remarkable voltage fluctuation suppression during normal generator operation.This innovation significantly enhances both unit-level and grid-wide voltage stability.

关键词

电压波动抑制/PSS/参数整定/龙滩电厂

Key words

voltage fluctuation suppression/PSS(power system stabilizer)/parameter tuning/Longtan Power Plant

分类

动力与电气工程

引用本文复制引用

韦怡,陈刚,赵勇,韦东梁,江出阳..龙滩电厂有效整定PSS抑制电压波动的研究与实践[J].红水河,2025,44(1):1-7,7.

红水河

1001-408X

访问量0
|
下载量0
段落导航相关论文