电力勘测设计Issue(3):26-30,5.DOI:10.13500/j.dlkcsj.issn1671-9913.2025.03.005
中冰区输电线路直线塔覆冰断线张力计算与分析
Calculation and Analysis of Line Breaking Tension of Transmission Line Suspension Tower Covered with Ice in Medium Ice Area
盛道伟 1梁明 1刘翰柱 1何世雄1
作者信息
- 1. 中国电力工程顾问集团西南电力设计院有限公司,四川 成都 610056
- 折叠
摘要
Abstract
Calculation and analysis of the broken line tension of the suspension tower in the medium ice area are conducted.The broken line tension of five-span and seven-span transmission lines in medium ice area is calculated under various conditions including icing rate,span,and insulator string length.The effects of icing rate,span,string length and sub conductor splitting number on the breaking tension are analyzed and compared with the values in the current regulations.Suggestions for the percentage of breaking tension of suspension towers in ultra-high voltage direct current transmission lines in medium ice area were proposed.关键词
输电线路/中冰区/断线张力/直线塔Key words
transmission line/medium icing area/breaking tension/suspension tower分类
动力与电气工程引用本文复制引用
盛道伟,梁明,刘翰柱,何世雄..中冰区输电线路直线塔覆冰断线张力计算与分析[J].电力勘测设计,2025,(3):26-30,5.