基于直流电压同步的构网型直驱风电机组暂态控制方法

邓桢彦 王晗 周少泽 曹云峰 王伟 蔡旭

电力系统自动化2025,Vol.49Issue(7):2-12,11.
电力系统自动化2025,Vol.49Issue(7):2-12,11.DOI:10.7500/AEPS20240228004

基于直流电压同步的构网型直驱风电机组暂态控制方法

Transient Control Method for Grid-forming Direct-drive Wind Turbine Unit Based on DC Voltage Synchronization

邓桢彦 1王晗 1周少泽 2曹云峰 1王伟 2蔡旭1

作者信息

  • 1. 电力传输与功率变换控制教育部重点实验室(上海交通大学),上海市 200240
  • 2. 国网电力科学研究院有限公司(南瑞集团有限公司),江苏省 南京市 211106
  • 折叠

摘要

Abstract

The power system with high proportion of renewable energy and high proportion of power electric equipment presents the characteristics of weak inertia and low short-circuit ratio,and the grid-following renewable energy cannot independently provide the transient frequency and voltage support required by the system.The adoption of grid-forming control is regarded as the key to solving this problem.Grid-forming converters manifest voltage source characteristics.However,due to the limited overcurrent capability of power devices,controlling transient currents during faults poses a challenge.Full-power direct-drive wind turbine units can employ DC voltage synchronization to achieve grid-forming,and an additional current controller is applied to suppress transient currents for fault ride-through.Nevertheless,this method still experiences impact currents during fault occurrence and recovery moments,risking the loss of transient support capability due to protection control strategy for converters.In response to this issue,by analyzing the short-circuit current generation mechanism and power response mechanism of grid-forming full-power wind turbine units using DC voltage synchronization during grid faults,an improved transient control method is proposed.The method employs a voltage vector limiter to achieve rapid matching of internal potential with fault voltage to limit the steady-state component of short-circuit current.Additionally,a nonlinear virtual resistor is introduced to achieve fast control of internal potential compensation to suppress the transient component of short-circuit current.Furthermore,during faults,the synchronization loop and reactive power loop are blocked to maintain the voltage source characteristics of the unit and achieve autonomous power response.The effectiveness and feasibility of the proposed method are verified through simulation and experimental validation.

关键词

构网型控制/风电机组/直流电压同步/暂态响应/短路电流

Key words

grid-forming control/wind turbine unit/DC voltage synchronization/transient control/short-circuit current

引用本文复制引用

邓桢彦,王晗,周少泽,曹云峰,王伟,蔡旭..基于直流电压同步的构网型直驱风电机组暂态控制方法[J].电力系统自动化,2025,49(7):2-12,11.

基金项目

国家重点研发计划资助项目(2022YFB2402703) (2022YFB2402703)

国家电网公司科技项目(52272222001J). This project is supported by National Key R&D Program of China(No.2022YFB2402703)and State Grid Corporation of China(No.52272222001J). (52272222001J)