电气技术2025,Vol.26Issue(4):80-84,5.
一起直流光电流互感器故障原因分析
Fault analysis of the direct current optical current transformer
陈宇飞 1金海望 1李金卜 1刘鹏 1柳杨1
作者信息
- 1. 国网冀北电力有限公司超高压分公司,北京 102488||河北省柔性直流输电装备与技术实证重点实验室,天津 300100
- 折叠
摘要
Abstract
DC optical current transformer(OCT)is an important equipment in high voltage direct current(HVDC)transmission project.Its safety and stability is of great significance to the power grid.In this paper,the causes of a DC optical current transformer fault at a converter station are analyzed and the possible location of the fault is investigated.Finally,it is determined that the change in the characteristic parameters of the fault is caused by the cracks produced after the long term deterioration of the optical fiber melting point.This work is of certain reference value for fault analysis of the OCT in engineering.关键词
直流输电/光电流互感器(OCT)/光纤劣化/故障Key words
direct current transmission/optical current transformer(OCT)/fiber deterioration/fault引用本文复制引用
陈宇飞,金海望,李金卜,刘鹏,柳杨..一起直流光电流互感器故障原因分析[J].电气技术,2025,26(4):80-84,5.