35 kV系统两种降低雷电入侵波大小的措施效果仿真对比

匡扶正 李景禄 吴泽文 伊国强

电瓷避雷器Issue(2):10-18,9.
电瓷避雷器Issue(2):10-18,9.DOI:10.16188/j.isa.1003-8337.2025.02.002

35 kV系统两种降低雷电入侵波大小的措施效果仿真对比

Simulation Comparison of the Effects of Two Measures to Reduce the Stress of Lightning Intrusion Waves in 35 kV System

匡扶正 1李景禄 1吴泽文 1伊国强1

作者信息

  • 1. 长沙理工大学大学电气与信息工程工程学院,长沙 410114
  • 折叠

摘要

Abstract

Aiming at the problem of damage to transformer and high-voltage arrester caused by lightning intrusion wave,firstly the harm caused by lightning wave to transformer and high-voltage arrester is ana-lyzed,and secondly,line arresters or protective gaps are installed on several base towers in front of the transformer high-voltage side to weaken the lightning intrusion wave to prevent equipment damage,and the effects of two measures are analyzed and compared.Based on ATP/EMTP software,a model of 35 kV lightning wave intrusion transformer is established,and the simulation results show that when the first base pole tower near the transformer is struck by lightning and causes a two-phase insulator flashover,the lightning intrusion wave will cause damage to the arrester on the high-voltage side.The installation of line arrester can weaken the lightning intrusion wave better than the installation protection gap,and the protection range of the line arrester is wider,and the research results have a certain guiding reference va-lue for the prevention and control of lightning intrusion wave in 35 kV line.

关键词

防雷/保护间隙/线路避雷器/雷电入侵波/ATP/EMTP

Key words

lightning protection/protection gaps/line arrester/lightning intrusion waves/ATP/EMTP

引用本文复制引用

匡扶正,李景禄,吴泽文,伊国强..35 kV系统两种降低雷电入侵波大小的措施效果仿真对比[J].电瓷避雷器,2025,(2):10-18,9.

电瓷避雷器

1003-8337

访问量0
|
下载量0
段落导航相关论文