流体机械2025,Vol.53Issue(3):104-109,6.DOI:10.3969/j.issn.1005-0329.2025.03.013
双循环除湿机系统性能优化
Performance optimization of dual-circulation air dehumidification system
摘要
Abstract
This study investigates performance optimization of dual-circulation air dehumidification system by analyzing compressor operating frequency and electronic expansion valve(EEV)opening configurations.A comprehensive thermodynamic model was developed to correlate EEV openings with critical performance indicators including refrigeration capacity,refrigerant mass flow rate,coefficient of performance(COP),and dehumidification capacity.Experimental validation confirmed the optimal compressor-EEV coordination patterns under specific operating conditions.The results demonstrate that maximum COP values occur at EEV openings of 18%,25%,and 30%corresponding to compressor frequencies of 38,42,and 45 Hz respectively,revealing a monotonically increasing relationship between optimal frequency and valve opening.System optimization achieved a COP enhancement from 0.993 to 1.817 through implementation of 42 Hz compressor operation with 25%EEV opening,representing an 83%efficiency improvement.The established control strategy provides a methodological framework for operational optimization of dual-circulation air dehumidification system under variable load conditions.关键词
双循环除湿机/电子膨胀阀/压缩机/能效比Key words
dual-circulation air dehumidification system/electronic expansion valve/compressor/coefficient of performance分类
通用工业技术引用本文复制引用
张楚烦,蔡慧,焦建格,蔡文剑..双循环除湿机系统性能优化[J].流体机械,2025,53(3):104-109,6.基金项目
浙江省自然科学基金联合基金项目(LZJWY24E090001) (LZJWY24E090001)