| 注册
首页|期刊导航|煤气与热力|燃气厂站总图设计中规范条款和规范用词的执行

燃气厂站总图设计中规范条款和规范用词的执行

叶志昊 张姝媛 张红燕

煤气与热力2025,Vol.45Issue(4):后插19-后插21,3.
煤气与热力2025,Vol.45Issue(4):后插19-后插21,3.

燃气厂站总图设计中规范条款和规范用词的执行

Implementation of Standard Clauses and Terms in General Layout Design of Gas Plants and Stations

叶志昊 1张姝媛 1张红燕2

作者信息

  • 1. 中国市政工程华北设计研究总院有限公司第十设计研究院,天津 300074
  • 2. 中国石油天然气股份有限公司规划总院,北京 100083
  • 折叠

摘要

Abstract

In the general layout design of gas plants and stations,it is crucial to correctly implement normative clauses and terms.Combined with the general layout design issues of engineering examples and in accor-dance with the provisions of article 3.4.12 of Code for Fire Protection Design of Buildings(2018 edition)(GB 50016-2014),by analyzing the normative term"should not",it is found that the distance between buildings in the factory area and the factory walls var-ies depending on the situation,and can be selected as less than 5 meters(which can be 0),equal to 5 meters,greater than 5 meters,or unrelated to this limit.

关键词

不宜/建筑/围墙/条文说明/防火间距

Key words

should not/building/wall/article descrip-tion/fire separation distance