| 注册
首页|期刊导航|煤气与热力|太阳能空气源热泵集成系统优化研究

太阳能空气源热泵集成系统优化研究

郝少校 王强 陈茹 刘凤珍 王玉博 葛建民

煤气与热力2025,Vol.45Issue(4):后插42-后插47,6.
煤气与热力2025,Vol.45Issue(4):后插42-后插47,6.

太阳能空气源热泵集成系统优化研究

Research on Optimization of Solar Air Source Heat Pump Integrated System

郝少校 1王强 1陈茹 2刘凤珍 1王玉博 1葛建民3

作者信息

  • 1. 山东建筑大学热能工程学院,山东济南 250101||山东省碳中和技术创新中心,山东济南 250101
  • 2. 山东省碳中和技术创新中心,山东济南 250101||山东省科学院生态研究所(山东省科学院中日友好生物技术研究中心),山东济南 250101
  • 3. 山东科灵节能装备股份有限公司,山东潍坊 262100
  • 折叠

摘要

Abstract

A solar air source heat pump integrated sys-tem(referred to as the integrated system)was designed.Taking the integrated system as the research,a system simulation model was built using TRNSYS software.Orthogonal test method was used to optimize the light-ing area of solar collector,the rated heat capacity of air source heat pump,the volume of the heat storage water tank and the power of heat pump circulation pump.The range analysis method was used to analyze the ex-perimental results.When the lighting area of the solar collector is 55 m2,the rated heat capacity of the air source heat pump is 11.4 kW,the volume of the heat storage water tank is 5 m3,and the power of the heat pump circulation pump is 143 W,the heating perfor-mance coefficient of the integrated system reaches 4.83,which is the best performance.A comparative analysis was conducted on the selection schemes of in-tegrated system before and after optimization.After op-timization,the conversion cost of the integrated system increases by 6.24%compared to before optimization,and the total lifecycle cost decreases by 10.55%com-pared to before optimization.The optimized integrated system has high economic and operational efficiency.

关键词

太阳能空气源热泵集成系统/正交试验法/极差分析法/全生命周期成本

Key words

solar air source heat pump integrated sys-tem/orthogonal test method/range analysis method/to-tal lifecycle cost

分类

建筑与水利

引用本文复制引用

郝少校,王强,陈茹,刘凤珍,王玉博,葛建民..太阳能空气源热泵集成系统优化研究[J].煤气与热力,2025,45(4):后插42-后插47,6.

煤气与热力

1000-4416

访问量0
|
下载量0
段落导航相关论文