节能2025,Vol.44Issue(2):10-13,4.DOI:10.3969/j.issn.1004-7948.2025.02.003
基于动态负荷的寒冷地区酒店建筑新风负荷计算及分析
Calculation and analysis of fresh air load of hotel building in cold area based on dynamic load
摘要
Abstract
Taking a three-star hotel in Jinan City as the research object,the building model of the hotel is established,the dynamic load of the air conditioning system is calculated,the characteristics of the fresh air load of the building is analyzed,and the energy waste of the fresh air system under different occupancy rates is discussed.The results show that the proportion of fresh air load in total heat load is 69.37%and that of sensible heat load is 68.81%due to the influence of temperature difference between indoor and outdoor.The decrease of the occupancy rate leads to a significant increase in the waste rate of fresh air energy consumption,with the average waste rate reaching 31.99%.Under winter operating conditions,the maximum energy waste rate of the fresh air system can reach 56.46%.关键词
酒店建筑/空调负荷/新风负荷/节能Key words
hotel building/air conditioning load/fresh air load/energy-saving分类
土木建筑引用本文复制引用
成嘉仪,孔令健,曹申辉,刘晶,张林华..基于动态负荷的寒冷地区酒店建筑新风负荷计算及分析[J].节能,2025,44(2):10-13,4.基金项目
山东省科技型中小企业创新能力提升工程项目(项目编号:2022TSGC1105) (项目编号:2022TSGC1105)