| 注册
首页|期刊导航|建筑结构学报|C100混凝土和Q550双钢板组合剪力墙受剪性能研究

C100混凝土和Q550双钢板组合剪力墙受剪性能研究

陈才华 赵英琦 邱盛源 王柏翔

建筑结构学报2025,Vol.46Issue(5):84-97,14.
建筑结构学报2025,Vol.46Issue(5):84-97,14.DOI:10.14006/j.jzjgxb.2024.0391

C100混凝土和Q550双钢板组合剪力墙受剪性能研究

Research on shear behavior of C100 concrete and Q550 double steel plate composite shear walls

陈才华 1赵英琦 2邱盛源 2王柏翔2

作者信息

  • 1. 中国建筑科学研究院有限公司,北京 100013||中建研科技股份有限公司,北京 100013
  • 2. 中国建筑科学研究院有限公司,北京 100013
  • 折叠

摘要

Abstract

To study the shear failure mode and bearing capacity of high-strength double steel plate composite shear walls,five scaled-down specimens with a scale ratio of 1∶4,a shear-span ratio of 1.0,C100 concrete and Q550 double steel plates were subjected to quasi-static tests.The effects of steel content ratio,axial compression ratio and stiffener spacing on their shear performance were analyzed.The test results show that the failure mode of all shear walls are compression-shear failure,and the final failure mode is steel web buckling,weld cracking and concrete diagonal crushing.The hysteretic curves of the shear walls are full and spindle-shaped,with peak drift ratios ranging from 1/85 to 1/57 and ultimate drift ratios ranging from 1/64 to 1/32,demonstrating good energy dissipation and deformation capabilities.Moreover,the higher the steel content ratio,the higher the lateral bearing capacity,and the smaller the stiffener spacing,the better the deformation capacity.A refined finite element model was established using the general finite element software ABAQUS,and the simulation results were in good agreement with the test results,with the error range of shear bearing capacity within 12%.Based on the finite element model,the influences of shear-span ratio ranging from 0.75 to 1.25,axial compression ratio ranging from 0.3 to 0.6,web thickness ranging from 3 to 5 mm,wall thickness ranging from 100 to 200 mm and stiffener spacing ranging from 84 to 172 mm on the shear performance of shear walls were studied.Three existing calculation formulas for the shear bearing capacity of steel plate shear walls were collected and compared with the test results.The results show that the existing formulas are conservative when calculating the shear bearing capacity of high-strength double steel plate composite shear walls.

关键词

组合剪力墙/C100混凝土/Q550钢材/拟静力试验/受剪性能/受剪承载力

Key words

composite shear wall/C100 concrete/Q550 steel/quasi-static test/shear behavior/shear capacity

分类

土木建筑

引用本文复制引用

陈才华,赵英琦,邱盛源,王柏翔..C100混凝土和Q550双钢板组合剪力墙受剪性能研究[J].建筑结构学报,2025,46(5):84-97,14.

基金项目

国家重点研发计划(2022YFC3802002),中国建筑科学研究院有限公司科研项目(20220122330730017),中建研科技股份有限公司科研项目(20221902970730032). (2022YFC3802002)

建筑结构学报

OA北大核心

1000-6869

访问量4
|
下载量0
段落导航相关论文