信号系统UPS设备供电维持能力分析
Analysis of Power Supply Maintenance Capability of UPS Equipment in Signaling System
摘要
Abstract
This paper takes the example of a certain signal equipment centralization station of Hangzhou Metro that has the train turning back function,and makes the assumption of primary load power failure on the two 0.4 kV mains supplies of the station,to calculate the power supply time of the backup power supply provided by the UPS power supply for the signaling system through the storage battery.Additionally,it presents calculations by means of the standard formula for storage batteries,which serve to prove that the backup power supply time of the signaling equipment provided by the storage battery under the rated working conditions is much longer than the value in the design requirements.Furthermore,in view of the actual field test situation,this paper presents theoretical analysis and practical testing on the switch throwing function of the UPS storage battery in the metro operation scenarios,which serve to obtain the limit times of switch throwing using the electric energy of storage batteries,so as to test the ability of UPS to maintain the normal operation of the signaling system and handle the turning back operation of trains in the case of mains supply power failure.关键词
信号系统/电源系统/不间断电源/蓄电池/道岔/列车折返/设备供电Key words
signaling system/power system/UPS/storage battery/switch/train turning back/equipment power supply分类
交通工程引用本文复制引用
梅满,田文礼,胡昊文..信号系统UPS设备供电维持能力分析[J].铁路通信信号工程技术,2025,22(5):94-100,7.基金项目
杭州市交通运输局2023年科研项目(Hzjt202306) (Hzjt202306)