煤气与热力2025,Vol.45Issue(5):67-71,5.
埋地钢质燃气管道强制电流阴极保护系统的设计
Design of Impressed Current Cathodic Protection System for Buried Steel Gas Pipeline
马英亮1
作者信息
- 1. 甘肃昆仑燃气有限公司,甘肃兰州 730000
- 折叠
摘要
Abstract
Taking outbound sub-high pressure pipeline of a gate station as the research object,an impressed current cathodic protection system is installed for bur-ied steel gas pipeline in service.The technology of im-pressed current cathodic protection is introduced,and the design and calculation method of impressed current cathodic protection system using a deep well anode ground bed is given.After the anode installation is complete,the grounding resistance of the measured deep well anode is 0.07 Ω.After the impressed current cathodic protection system is put into operation,the to-tal resistance of the cathodic protection system circuit is calculated to be 6.48 Ω based on the data displayed on the potentiostat.The power-off potential of each test pile is in the range of-1.2 and-0.85V,achieving the protective effect,which proves that this method is effec-tive and relatively accurate,and provides a basis for the design of deep well anodes in the future.关键词
阴极保护系统/深井阳极地床/强制电流/城镇燃气管道Key words
cathodic protection system/deep well an-ode ground bed/impressed current/urban gas pipeline分类
土木建筑引用本文复制引用
马英亮..埋地钢质燃气管道强制电流阴极保护系统的设计[J].煤气与热力,2025,45(5):67-71,5.