| 注册
首页|期刊导航|宁夏电力|铜铝过渡线夹异常开裂原因分析及措施

铜铝过渡线夹异常开裂原因分析及措施

徐冬梅 周宇通 张杰 赵洲峰 罗宏建

宁夏电力Issue(2):77-82,6.
宁夏电力Issue(2):77-82,6.DOI:10.3969/j.issn.1672-3643.2025.02.012

铜铝过渡线夹异常开裂原因分析及措施

Analysis and measures of cracking of copper-aluminum transition clamp

徐冬梅 1周宇通 1张杰 1赵洲峰 1罗宏建1

作者信息

  • 1. 国网浙江省电力有限公司电力科学研究院,浙江 杭州 310014
  • 折叠

摘要

Abstract

To clarify the cause of the abnormal cracking of copper-aluminum transition clamp used in distribution network,studies were carried on the basis of macroscopic inspection,spectral analysis,and microstructure examination.From the perspective of atomic binding force,the four copper-aluminum transition clamps were found to have the unfused defect,the area of which is accounts for 64%,21%,30%and 5%,respectively.It is concluded that the crack-ing of copper-aluminum transition clamp could be connected with the force,discharge and corrosion,while the essential reason is the existence of unfused defect.The corresponding suggestions are put forward accordingly.

关键词

铜铝过渡线夹/开裂/对接焊缝/未熔合

Key words

copper-aluminum transition clamp/cracking/butt weld/unfused defect

分类

动力与电气工程

引用本文复制引用

徐冬梅,周宇通,张杰,赵洲峰,罗宏建..铜铝过渡线夹异常开裂原因分析及措施[J].宁夏电力,2025,(2):77-82,6.