Analysis and Handling of a High-Voltage Motor Trip Accident Caused by DC Grounding

张帅 1马华明 1常新海1

作者信息

  • 1. 酒钢(集团)宏晟电热公司,甘肃 嘉峪关 735100
  • 折叠

摘要

Abstract

An analysis of a high-voltage motor trip accident caused by two-point DC ground-ing revealed that steam infiltration into the motor's emergency button box led to condensation in win-ter,forming two grounding points of different polarities,which triggered the trip and load reduction.Further analysis confirmed that the mismatch between DC grounding resistance and the anti-jump relay setting was the root cause.Solutions such as sealing steam leakage points,adjusting the anti-jump relay setting,and strengthening insulation supervision were proposed.This case provides prac-tical insights for preventing DC system faults.

关键词

直流接地/防跳继电器/绝缘监督

Key words

DC grounding/anti-jump relay/insulation supervision