| 注册
首页|期刊导航|宁夏电力|500kV变电站隔离开关异常发热原因分析

500kV变电站隔离开关异常发热原因分析

谭晓蒙 史贤达 陈浩 田峰

宁夏电力Issue(3):64-68,5.
宁夏电力Issue(3):64-68,5.DOI:10.3969/j.issn.1672-3643.2025.03.010

500kV变电站隔离开关异常发热原因分析

Analysis of abnormal heating of disconnector in 500 kV substation

谭晓蒙 1史贤达 1陈浩 1田峰1

作者信息

  • 1. 内蒙古电力(集团)有限责任公司内蒙古电力科学研究院分公司,内蒙古 呼和浩特 010020
  • 折叠

摘要

Abstract

This study addresses the issue of abnormal large-scale heating at the flexible connection conductive strip of the upper and lower conductive tube joints in a GW6-type disconnector at a 500 kV substation.Through comprehensive analysis,including macroscopic observation,chemical composition analysis,scanning electron microscopy(SEM),and coating thickness testing of the replaced elbow fittings and conductive strips,it was found that insufficient tinning width at the copper conductive strip joints led to direct contact between the copper sheets and aluminum fittings.This caused electrochemical corrosion on the conductive contact surface of the aluminum fittings,increasing the contact resistance and resulting in abnormal heating during operation.To resolve this issue,it is recommended to replace the conductive strips of this disconnector type and install copper-aluminum transition plates.Additionally,regular infrared temperature monitoring should be implemented to reduce the probability of abnormal heating at the joints,ensuring the safe and stable operation of the equipment.

关键词

GW6型隔离开关/导电带/电化学腐蚀/接触电阻/铜铝过渡板

Key words

GW6 disconnector/conductive tape/electrochemical corrosion/contact resistance/copper-aluminum tran-sition plate

分类

金属材料

引用本文复制引用

谭晓蒙,史贤达,陈浩,田峰..500kV变电站隔离开关异常发热原因分析[J].宁夏电力,2025,(3):64-68,5.

基金项目

内蒙古电力(集团)有限责任公司科技项目(KJ202208) (集团)

宁夏电力

1672-3643

访问量0
|
下载量0
段落导航相关论文