| 注册
首页|期刊导航|电气传动|基于折反射行波相关性分析的配电电缆单相接地故障测距

基于折反射行波相关性分析的配电电缆单相接地故障测距

纪良 徐军 管亚 崔景侠 何杰 潘艺航

电气传动2025,Vol.55Issue(7):70-77,8.
电气传动2025,Vol.55Issue(7):70-77,8.DOI:10.19457/j.1001-2095.dqcd25921

基于折反射行波相关性分析的配电电缆单相接地故障测距

Single-phase Grounding Fault Distance Measurement of Distribution Cable Based on Refraction-reflection Traveling Wave Correlation Analysis

纪良 1徐军 1管亚 1崔景侠 1何杰 1潘艺航2

作者信息

  • 1. 国网江苏省电力有限公司连云港供电分公司,江苏 连云港 222000
  • 2. 中国矿业大学电气工程学院,江苏 徐州 221000
  • 折叠

摘要

Abstract

The three-core underground cable in the distribution network works in a harsh environment.Due to the influence of aging,external force,high temperature and humidity,the insulation of long-term live operation is easily damaged and causes faults.Aiming at the single-phase grounding fault of cable in distribution network,a fault location method based on the refraction-reflection characteristics of traveling wave head was proposed.Firstly,the zero-mode voltage of each line was obtained,and the arrival time of the wave head was determined.The waveform in a power frequency period after the arrival of the wave head was selected,and the main frequency of the wave head was determined.The square wave with the same frequency as the main frequency of the wave head was selected as the initial traveling wave signal,and the attenuation signal waveform at the head and end of the initial traveling wave signal after refraction of different times at this frequency was calculated.If the correlation between the corresponding data of the waveform calculated at both ends met the requirements,it was assumed that the fault point is the actual fault point.Otherwise,continue to narrow the fault interval until the correlation between the waveform data is satisfied.Simulation results show that the method can quickly and accurately realize fault distance measurement,reduce the complexity of fault distance measurement,and has strong effectiveness and practicability.

关键词

配电电缆/故障测距/波形相似度/波头折反射

Key words

distribution cables/fault distance measurement/waveform similarity/wavehead refraction reflection

分类

信息技术与安全科学

引用本文复制引用

纪良,徐军,管亚,崔景侠,何杰,潘艺航..基于折反射行波相关性分析的配电电缆单相接地故障测距[J].电气传动,2025,55(7):70-77,8.

基金项目

江苏省碳达峰碳中和科技创新专项资金(BE2022609) (BE2022609)

电气传动

1001-2095

访问量0
|