电气技术2025,Vol.26Issue(7):76-80,5.
一起500 kV变电站直流系统异极窜电故障分析与模型推算
Analysis and model calculation of the inter-pole short circuit fault in DC system of a 500 kV substation
祝石厚 1张敏1
作者信息
- 1. 国网浙江省电力有限公司绍兴供电公司,浙江 绍兴 312000
- 折叠
摘要
Abstract
This paper introduces the analysis process of a 500 kV substation DC system inter-pole short circuit fault.In order to deeply explore this special kind of DC insulation fault,based on the balance bridge principle of the DC insulation monitor,a circuit model of the DC inter-pole short circuit is established,and the process of obtaining the short circuit resistance of mutual short circuit is given.By calculating and analyzing the relationship between the control bus voltage and the short circuit resistance during DC inter-pole short circuit,the characteristics of DC inter-pole short circuit are summarized to provide reference for handling similar DC system faults.关键词
绝缘监测仪/直流系统/直流接地/直流异极窜电Key words
insulation monitoring device/DC system/DC grounding/DC inter-pole short circuit引用本文复制引用
祝石厚,张敏..一起500 kV变电站直流系统异极窜电故障分析与模型推算[J].电气技术,2025,26(7):76-80,5.