制冷2025,Vol.44Issue(5):18-24,27,8.DOI:10.3969/J.ISSN.1005-9180.2025.05.0005
湛江吴川国际机场制冷空调系统增效降耗实践与探索
Practices and Explorations on Energy Efficiency Enhancement and Consumption Reduction of Refrigeration and Air Conditioning Systems at Zhanjiang Wuchuan International Airport
郭勇 1许杰 1郭林文 1赵骥1
作者信息
- 1. 广东省建筑设计研究所集团有限责任公司,广东 广州,510010
- 折叠
摘要
Abstract
This paper focuses on the energy efficiency enhancement and consumption reduction of the refrigeration and air conditioning system at Zhanjiang Wuchuan International Airport.It elaborates on the design practices in annual load calculation,cooling source equipment selection,distribution system optimization,innovative control strategies,and the integration of flight information with the air conditioning system.The objective is to improve the energy efficiency of the refrigeration plant.Field test data demonstrate that the adoption of high-efficiency refrigeration plant technology has elevated the annual comprehensive Energy Efficiency Ratio(EER)to over 5.4,achieving a 35~40%improvement compared to conventional systems.This study systematically summarizes energy efficiency enhancement pathways for refrigeration plants in terminal buildings located in high-temperature and high-humidity regions,providing valuable references for similar projects.关键词
航站楼/高效制冷机房/能效提升/控制策略/航班信息联动技术Key words
Terminal Building/High-Efficiency Chilled Water Plant/Energy Efficiency Improvement/Control Strategy/Flight Information Integration Technology分类
建筑与水利引用本文复制引用