制冷2025,Vol.44Issue(5):40-45,6.DOI:10.3969/J.ISSN.1005-9180.2025.05.0010
多联机室外机在超高层受限空间布置的散热模拟分析与优化
Heat Dissipation Simulation Analysis and Optimization of Multi-Connected Outdoor Units in Ultra-high-rise Restricted Space Arrangement
江宋标 1郭勇 1范济荣 1施时雨1
作者信息
- 1. 广东省建筑设计研究院集团股份有限公司,广州,510627
- 折叠
摘要
Abstract
A super high-rise building in Guangzhou is taken as the research object to analyze the heat dissipation performance of the air-cooled variable refrigerant flow system outdoor unit set up in the recessed restricted space of the building through numerical simulation.The study simulates three typical platform configurations(platform 1-E,2-W,2-S),from analyzing the return air temperature,local heat accumulation effect and the influence of external building components on airflow organization.Through the simulation of the building wind field and the equipment heat dissipation model,the heat dissipation effect of different outdoor unit platforms is analyzed and optimization suggestions are made.The results show that the reasonable design of the depth of the outdoor unit platform and the optimization of the fresh air make-up path,as well as the selection of equipment with a high shutdown protection temperature,can effectively improve the heat dissipation effect and ensure the reliable operation of the air conditioning system.关键词
风冷变制冷剂流量系统/超高层建筑/散热模拟/受限空间优化Key words
Air-cooled Variable Refrigerant Flow System/Ultra-high-rise Building/Heat Dissipation Simulation/Constrained Space Optimization分类
建筑与水利引用本文复制引用