石油石化绿色低碳2025,Vol.10Issue(5):65-71,7.DOI:10.20131/j.cnki.syshlsdt.20250916.001
锅炉风挡板执行机构部件改造及优化
Boiler Air Baffle Actuator Component Modification and Optimization
袁亮 1韩会亮 1魏代荣 1张建文 1祝敏敏1
作者信息
- 1. 中国石化塔河炼化有限责任公司,新疆库车 842000
- 折叠
摘要
Abstract
During the operation of a refining 75 t/h gas boiler,problems such as exceeding the limits of operating parameters,jamming of boiler induced draft flapper valve position,and abnormal vibration of induced draft actuator rod occurred from time to time,which affected its safe operation.Based on this,the two linking clips and one connecting rod of the boiler induced draft flapper actuator were modified.After the modification,actuator vibrations were significantly reduced,and issues like jerky movement and sudden position jumping were eliminated.Parameter fluctuations during adjustment and steady-state operation drastically decreased,with all parameter stability levels exceeding 99%,and thermal efficiency improved.The retrofit successfully achieved its goals of safer,more stable,and optimized boiler operation,providing a reference for similar boilers.关键词
改造/振动值/锅炉参数/稳定度/热效率/连杆振动/运行优化Key words
retrofit/vibration value/boiler parameters/stability/thermal efficiency/connecting rod vibration/operation optimization分类
能源科技引用本文复制引用
袁亮,韩会亮,魏代荣,张建文,祝敏敏..锅炉风挡板执行机构部件改造及优化[J].石油石化绿色低碳,2025,10(5):65-71,7.