| 注册
首页|期刊导航|理化检验-物理分册|气体绝缘封闭组合开关壳体泄漏原因

气体绝缘封闭组合开关壳体泄漏原因

XIE Zongxi YE Jianfeng SHI Yakun TIAN Ze TIAN Guoqing XUE Huan

理化检验-物理分册2025,Vol.61Issue(12):77-81,85,6.
理化检验-物理分册2025,Vol.61Issue(12):77-81,85,6.DOI:10.11973/lhjy-wl250177

气体绝缘封闭组合开关壳体泄漏原因

Leakage causes of the housing for gas-insulated closed combination switches

XIE Zongxi 1YE Jianfeng 2SHI Yakun 3TIAN Ze 2TIAN Guoqing 4XUE Huan5

作者信息

  • 1. State Grid Hubei Electric Power Co.,Ltd.,Wuhan 430040,China
  • 2. State Grid Hubei Electric Power Research Institute,Wuhan 430075,China
  • 3. Hubei Fangyuan Dongli Electric Power Science&Research Co.,Ltd.,Wuhan 430070,China
  • 4. CSSC Huangpu Wenchong Shipbulding Co.,Ltd.,Guangzhou 510700,China
  • 5. Hubei University of Technology,Wuhan 430086,China
  • 折叠

摘要

Abstract

The SF6 gas leakage fault occurred in the air chamber housing of a gas insulated closed combination switches.The causes of the leakage of the gas insulated switchgear housing were analyzed by means of macroscopic relationship,penetration detection,X-ray digital imaging detection,chemical composition analysis,mechanical property test,metallographic examination,scanning electron microscope and energy spectrum analysis,finite element simulation analysis.The results show that the content of Al and Si elements in the local area was high.During the casting process,the housing material produced loose and porosity defects,and the defects were not completely removed during the repair welding.Under the combined action of internal medium stress and welding residual stress,the housing cracked and produced penetrating defects,which eventually led to leakage failure of the housing.

关键词

气体绝缘封闭组合开关/泄漏/疏松/气孔/残余应力

Key words

gas-insulated closed combination switch/leakage/loose/porosity/residual stress

分类

通用工业技术

引用本文复制引用

XIE Zongxi,YE Jianfeng,SHI Yakun,TIAN Ze,TIAN Guoqing,XUE Huan..气体绝缘封闭组合开关壳体泄漏原因[J].理化检验-物理分册,2025,61(12):77-81,85,6.

基金项目

国网湖北电科院2024年材料专项项目(B11532244341) (B11532244341)

理化检验-物理分册

1001-4012

访问量0
|
下载量0
段落导航相关论文