制冷技术2025,Vol.45Issue(5):66-71,6.DOI:10.3969/j.issn.2095-4468.2025.05.205
喷淋冷却对多联机性能影响的实验研究
Experimental Study on Impact of Spray Cooling on Performance of Variable Refrigerant Flow Systems
摘要
Abstract
The spray cooling is proposed to improve the poor heat dissipation capacity of variable refrigerant flow(VRF)systems in small space,and the impact of spray cooling on performance of VRF is experimentally studied.The results show that the spray cooling system can effectively improve the heat dissipation capacity of the VRF and the saturated condensing pressure of the outdoor unit's refrigerant R410A has decreased from 3.6 MPa to 2.6 MPa.Under the working condition of 40-45 ℃,the VRF's cooling capacity is increased by about 15%,reaching 95%of its rated cooling capacity,and the energy consumption of the VRF is reduced by 12%.The water consumption of the spray device during the test period is approximately 60 kg/h.关键词
喷淋冷却系统/实测研究/制冷能力提升/运行节能Key words
Spray cooling system/Experimental Study/Increased cooling capacity/Operational energy saving分类
通用工业技术引用本文复制引用
FAN Wenke,LIN Bo..喷淋冷却对多联机性能影响的实验研究[J].制冷技术,2025,45(5):66-71,6.基金项目