| 注册
首页|期刊导航|高压电器|基于CFD模拟的全户内模块化变电站室内通风散热及气流组织优化设计

基于CFD模拟的全户内模块化变电站室内通风散热及气流组织优化设计

石慧 陈磊 孙应春 钱宇昊 李雨菲 刘志坚 史亚鑫

高压电器2026,Vol.62Issue(1):50-59,78,11.
高压电器2026,Vol.62Issue(1):50-59,78,11.DOI:10.13296/j.1001-1609.hva.2026.01.007

基于CFD模拟的全户内模块化变电站室内通风散热及气流组织优化设计

Optimization Design of Ventilation,Heat Dissipation and Airflow Organization for Fully Indoor Modular Substations Based on CFD Simulation

石慧 1陈磊 1孙应春 2钱宇昊 1李雨菲 1刘志坚 3史亚鑫3

作者信息

  • 1. 国网扬州供电公司,江苏 扬州 225001
  • 2. 扬州浩辰电力设计有限公司,江苏 扬州 225001
  • 3. 华北电力大学(保定),河北 保定 071003
  • 折叠

摘要

Abstract

The fully indoor modular 110 kV smart substation,due to its limited indoor space and concentrated heat-ing of electrical equipment,has exposed such problems as high indoor average temperature,excessive partial tem-perature and difficult temperature and humidity control,which is not conducive to the efficient and safe operation of electrical equipment.Therefore,in this paper the indoor dissipation and airflow organization effect is improved by controlling the inlet and outlet parameters.First,the current status of ventilation and heat dissipation in standard-ized design and prefabricated construction of substation as well as the heat generation of electrical equipment are analyzed.Then,overall 3D physical model of the substation is set up based on the real situation and the tempera-ture field distribution as well as air flow distribution of simulation are simulated and modeled.The numerical simu-lation results show that the average indoor temperature is 48℃,which is higher than the indoor temperature design requirements in 110-A2-6 design scheme,in which the average temperature of the capacitor compartment is the highest,which is 55℃when the fan is not operated.It is found through the analysis of the velocity field that the air flow rate near the electrical equipment is less than 1 m/s,and the indoor airflow vortex nearly coincides with the high temperature area.Finally,the design of the optimization scheme is performed.Since the temperature of the the capacitor compartment after switching on the axial fan is 45℃and as for the characteristics of the capacitor com-partment as well as ensuring its constant ventilation volume,three optimization schemes are propsoed by changing the size and position distribution with consideration of the air flow organization distribution.It is found by compari-son that the ventilation system natural air inlet+mechanical exhaust is arranged on the same side,the air outlet is arranged above the disconnector frame by the ventilation tube and the shutter width ratio is increased 0.48,the tem-perature in the capacitor compartment can be reduced to 37℃,which provides a case reference to solve the prob-lem of ventilation and heat dissipation in fully indoor modular substation.

关键词

模块化变电站/散热通风/气流组织/优化设计

Key words

modular substation/heat dissipation and ventilation/air-flow organization/optimization design

引用本文复制引用

石慧,陈磊,孙应春,钱宇昊,李雨菲,刘志坚,史亚鑫..基于CFD模拟的全户内模块化变电站室内通风散热及气流组织优化设计[J].高压电器,2026,62(1):50-59,78,11.

基金项目

国网江苏省电力有限公司自主科技项目(J2021223).Project Supported by Technology Project Independence of State Grid Jiangsu Electric Power Co.,Ltd.(J2021223). (J2021223)

高压电器

1001-1609

访问量0
|
下载量0
段落导航相关论文