制冷2025,Vol.44Issue(6):34-36,3.DOI:10.3969/J.ISSN.1005-9180.2025.06.0009
华南地区地铁高效空调系统节能方案研究
Research On Energy-saving Strategies For High-efficiency HVAC Systems For Metro in South China
龚胜强 1王静伟 1廖佳仪 1李小波1
作者信息
- 1. 广州地铁设计研究院股份有限公司,广东 广州,510030
- 折叠
摘要
Abstract
With the continuous expansion of subway line operations,the air conditioning system,as a major energy consumer in subways,has made effective energy-saving operation an urgent issue.The author takes a standard 6-carriage station in South China as the research subject,analyzing and studying economically reasonable configurations for water system equipment and energy-efficient operational modes.Since the supply and return temperatures of cooling water are closely related to the energy efficiency of the air conditioning system,lowering the cooling water outlet temperature can significantly improve the efficiency of chillers.However,this requires a corresponding increase in the heat dissipation capacity of cooling towers.This paper comprehensively analyzes and compares the advantages and disadvantages of reducing cooling water supply and return temperatures for subway projects,proposing an appropriate cooling water supply and return temperature of 30.5/35.5 ℃.关键词
地铁/高效空调/节能/经济性Key words
Metro/High-efficiency HVAC/Energy-saving/Cost-effectiveness分类
通用工业技术引用本文复制引用
龚胜强,王静伟,廖佳仪,李小波..华南地区地铁高效空调系统节能方案研究[J].制冷,2025,44(6):34-36,3.