On-site tests were conducted on the heat transfer coefficient of the exterior walls of a passive of-fice building(hereinafter referred to as the passive house)in Harbin,a typical city in severe cold regions.Meanwhile,the indoor temperature and energy con-sumption under intermittent heating during the late stage of the heating season were monitored,and simula-tion analysis was conducted for the indoor temperature and heating energy consumption.The test results show that the heat transfer coefficient of the external walls is 0.112 W/(m2·K),which meets the design require-ments.On-site measurements during the late heating period indicate that the indoor temperature change un-der intermittent heating is relatively stable.With the increase of floors,the indoor temperature shows an up-ward trend.The daily average indoor temperatures of the 1st to 5th floors are 18.0,19.0,19.4,20.6,and 22.5 ℃ respectively,all meeting the minimum indoor heating temperature requirements.The simulation re-sults suggest that intermittent heating can be adopted for passive office buildings in severe cold regions dur-ing the early and late heating periods,and heating is recommended between 7:00-11:00 and 13:00-17:00.During the mid-stage of the heating season,when the outdoor temperature is relatively low,continuous heat-ing on working days and shutdown on weekends are recommended.The annual heating energy consumption under the recommended heating mode is 13.08 kW·h/(m2·a),which saves 40.4%compared with the continu-ous heating mode.

关键词

外墙传热系数/间歇供暖/建筑能耗/被动房/严寒地区

Key words

heat transfer coefficient of external wall/in-termittent heating/building energy consumption/pas-sive house/severe cold region

分类

建筑与水利

引用本文复制引用

杨宇鑫,王昭俊,刘畅,高鹏程..严寒地区被动房外墙传热系数与供暖能耗分析[J].煤气与热力,2026,46(1):7-12,6.

煤气与热力

1000-4416

访问量0
|
下载量0
段落导航相关论文