宁夏电力Issue(1):68-73,79,7.DOI:10.3969/j.issn.1672-3643.2026.01.010
一起换流站GIS断路器设备内部放电故障分析
Analysis of an internal discharge fault in a GIS circuit breaker at a converter station
赵希洋 1刘书吉 1牛勃 2李昊 1罗海贵 1王旭光3
作者信息
- 1. 国网宁夏电力有限公司超高压公司,宁夏 银川 750011
- 2. 国网宁夏电力有限公司电力科学研究院,宁夏 银川 750011
- 3. 西安西电开关电气有限公司,陕西 西安 710077
- 折叠
摘要
Abstract
An internal discharge fault occurred in an 800 kV gas-insulated switchgear(GIS)circuit breaker at a con-verter station.To identify the discharge path and root cause,comprehensive investigations were carried out,including disassembly inspection,electric field simulation,and insulation operating rod simulation tests.The results indicate that the fault was caused by partial discharge induced by a foreign object inside the enclosure,which led to local electric field distortion.Corresponding mitigation measures are proposed to prevent the recurrence of similar discharge failures,providing a reference for the safe operation and maintenance of GIS equipment.关键词
异物放电/电场仿真/特高频检测Key words
foreign matter discharge/electric field simulation/ultra-high-frequency(UHF)detection分类
信息技术与安全科学引用本文复制引用
赵希洋,刘书吉,牛勃,李昊,罗海贵,王旭光..一起换流站GIS断路器设备内部放电故障分析[J].宁夏电力,2026,(1):68-73,79,7.