相变蓄热太阳能空气源热泵复合供暖性能研究

Study on Combined Heating Performance of Phase-Change Thermal Storage Solar Air-Source Heat Pump

贾孝志 1王强 1周宇 2江红阳 3刘凤珍 1周长庚 3王玉博1

作者信息

  • 1. 山东建筑大学 热能工程学院,山东济南 250101||山东省碳中和技术创新中心,山东济南 250101
  • 2. 山东省碳中和技术创新中心,山东济南 250101||山东省科学院生态研究所,山东济南 250101
  • 3. 华春新能源股份有限公司,山东济宁 272100
  • 折叠

摘要

Abstract

A solar air-source heat pump combined heat-ing system with a phase-change thermal storage water tank(hereinafter referred to as the combined heating system)is proposed.The air-source heat pump in the system is equipped with a defrosting heat exchanger,enabling heating while defrosting.The conventional combined heating system(without phase-change mate-rials in the hot water storage tank,and the air-source heat pump not equipped with a defrosting heat ex-changer,only realizing defrosting by switching the flow direction of the refrigerant through a four-way valve)is taken as the comparison system.Combined with practi-cal cases,a simulation method is used to comparatively analyze the indoor temperature stability,power con-sumption,and system coefficient of performance(COP)of the two systems,and simulate and calculate the heating proportion of the solar collector,phase-change thermal storage water tank,and air-source heat pump in the combined heating system.Compared with the conventional combined heating sys-tem,the combined heating system can maintain stable indoor temperature during the defrosting phase,effec-tively improving heating quality.The power consump-tion of the combined heating system during the heating period is 1,822.38 kW·h,while that of the conven-tional combined heating system is 2,105.19 kW·h.Compared with the conventional combined heating sys-tem,the power consumption of the combined heating system during the heating period is reduced by 13.4%.The monthly COP of the combined heating system is higher than that of the conventional combined heating system.The average COP of the combined heating sys-tem and the conventional combined heating system dur-ing the heating period is 3.58 and 3.16.The combined heating system mainly uses phase-change heat storage water tank and air-source heat pump for heating at night.With the increase of the heating proportion of so-lar collectors at sunrise,it can completely rely on solar collectors for heating around noon.

关键词

太阳能空气源热泵/复合供暖/相变蓄热/除霜

Key words

solar air-source heat pump/combined heat-ing/phase-change thermal storage/defrosting

分类

建筑与水利

引用本文复制引用

贾孝志,王强,周宇,江红阳,刘凤珍,周长庚,王玉博..相变蓄热太阳能空气源热泵复合供暖性能研究[J].煤气与热力,2026,46(2):15-20,6.

基金项目

山东省科技型中小企业创新能力提升项目(2023TSGC0326) (2023TSGC0326)

煤气与热力

1000-4416

访问量3
|
下载量0
段落导航相关论文