电力勘测设计Issue(2):54-60,7.DOI:10.13500/j.dlkcsj.issn1671-9913.2026.02.009
湿陷性黄土场地输电线路基础抗拔安全储备系数优化设计
Optimization Design of the Safety Reserve Coefficient for the Pull-out Resistance of Transmission Line Foundations in Collapsible Loess Sites
韩绍康 1黄利平 1彭韶男 2文凡 1杨磊 1魏志康3
作者信息
- 1. 中国电力工程顾问集团西北电力设计院有限公司,陕西 西安 710075
- 2. 中国电力工程顾问集团新能源有限公司西安分公司,陕西 西安 710032
- 3. 重庆大学,重庆 400044
- 折叠
摘要
Abstract
The design of transmission line foundations on collapsible loess sites presents significant challenges due to the complex interactions among soil collapsibility and softening,non-uniform settlement,and dynamic loading.This study investigates the progressive damage mechanism at the foundation-soil interface in collapsible loess environments by developing a water-mechanical coupling constitutive model and performing detailed finite element simulations.To enhance design reliability and efficiency,a multi-objective optimization approach for safety factors based on reliability theory is introduced,and the proposed method is validated through in-situ testing.The research establishes a theoretical framework that effectively balances structural safety and economic feasibility for transmission line foundation design in collapsible loess regions,addressing the fundamental inconsistency between conventional static safety factors and the dynamic behavior of collapsible soils.关键词
湿陷性黄土/抗拔基础/安全储备系数/参数优化/有限元分析Key words
collapsible loess/uplift resistance foundation/safety reserve coefficient/parameter optimization/finite element analysis分类
能源科技引用本文复制引用
韩绍康,黄利平,彭韶男,文凡,杨磊,魏志康..湿陷性黄土场地输电线路基础抗拔安全储备系数优化设计[J].电力勘测设计,2026,(2):54-60,7.