When the fault occurs in the neutral region of the voltage source converter(VSC)based DC grid with true bipolar structure,the fault current may be very small,and the traditional differential protection cannot identify the fault.For the above problem,it first-ly analyzes the fault characteristics of four-terminal VSC based DC grid neutral zone,and the working principles of the metal loop monitoring device and introduces the grounding resistance and impedance monitoring device.Combined with the pole control protection device,it proposes a protection strategy for the neutral area metal ground fault of the true bipolar VSC based DC grid,by adjusting the bipolar operation status and system ground to increase the fault current,so that it enables the protection to act and isolate the fault.Fi-nally,it establishes a four-terminal VSC based DC grid model through MATLAB,which verifies the effectiveness of this strategy for the neutral area metal ground fault of the true bipolar VSC based DC grid.

关键词

柔性直流电网/中性区域接地故障/金属回线监视/接地电阻阻抗监视

Key words

VSC based DC grid/neutral grounding fault/metal loop monitoring device/grounding resistance and impedance moni-toring device

分类

信息技术与安全科学

引用本文复制引用

李金卜,张荣博,王卫龙,陈思宇,杨杰..真双极柔性直流电网中性区域金属性接地故障保护策略[J].东北电力技术,2026,47(3):14-19,6.

东北电力技术

1004-7913

访问量0
|
下载量0
段落导航相关论文