高压电器2026,Vol.62Issue(4):229-236,8.DOI:10.13296/j.1001⁃1609.hva.2026.04.027
微粒缺陷引发220 kV GIS绝缘击穿的事故分析及预防措施
Analysis and Preventive Measures of Insulation Breakdown Accident Caused by Particle Defects in 220 kV GIS
雷志城 1黄烜城 1黄涛 1陈敏哲 1刘雨 1石仁强1
作者信息
- 1. 江苏方天电力技术有限公司,南京 211102
- 折叠
摘要
Abstract
GIS is one of critical equipment of power system and its safe and reliable operation is very important.The insulation breakdown in cable compartment of 220 kV GIS in a power plant is analyzed.It is concluded by the judgement of the fault recording diagram that single⁃phase grounding short circuit occurs firstly,followed by the three⁃phase short circuit.Based on the disintegration and detection,the accident process is analyzed as follows:dur⁃ing operation,foreign particle drops in the gas compartment and enters into the strong electric field area of the cable compartment,leading to electric field distribution and single⁃phase breakdown.Since no insulating barrier is set be⁃tween the cable compartment and the gas compartment of disconnector,the molten metal splashes onto the support spacer of the earthing switch after a single⁃phase breakdown,leading to the escalation of the accident and resulting in a three⁃phase short circuit.Drawing lessons from the accident,such preventive measures as selecting stainless steel adsorbent box,reasonably reserving insulation margin of non⁃standard parts in GIS,strengthening patrolinspec⁃tion and assessment of equipment status are proposed so to provide practical basis for safe operation and design opti⁃mization of GIS in the future.关键词
GIS绝缘击穿/解体分析/异物掉落/电场畸变/预防措施Key words
insulation breakdown in GIS/disintegration analysis/dropped particle/electric field distortion/preventive measures引用本文复制引用
雷志城,黄烜城,黄涛,陈敏哲,刘雨,石仁强..微粒缺陷引发220 kV GIS绝缘击穿的事故分析及预防措施[J].高压电器,2026,62(4):229-236,8.