摘要
Abstract
As one of the auxiliary systems for small inland research reactors,the water supply supporting system includes the equipment cooling water system and the softened desalinated water system.The equipment cooling water system is mainly responsible for providing low-temperature cooling water to heat exchange equipment in the main process system,while the softened desalinated water system is mainly responsible for providing desalinated water for make-up and equipment flushing in the main process system.The equipment cooling water system needs to first determine the final heat sink form of the equipment cooling water system based on the water quality of the local water source,environmental impact assessment,meteorological conditions,etc.,thereby determining the specific settings of the system;the softened desalinated water system determines the settings of the system by considering several factors,including the degree of equipment integration,the floor area of the machine room,the degree of automated operation,the labor cost for later maintenance,the initial investment of equipment,and the production and installation cycle of equipment procurement.关键词
最终热阱/系统流程图/设备配置情况/方案对比研究/阴阳离子置换工艺/双级反渗透+EDI工艺Key words
final heat trap/system flow chart/equipment configuration/scheme comparison study/anion and cation displacement process/dual-stage reverse osmosis+EDI process分类