| 注册
首页|期刊导航|能源工程|基于热路解析模型的山区光伏电站直埋电缆载流量计算及影响因素分析

基于热路解析模型的山区光伏电站直埋电缆载流量计算及影响因素分析

谢伟东 肖钢 马自伟

能源工程2026,Vol.46Issue(2):82-86,5.
✕
能源工程2026,Vol.46Issue(2):82-86,5.DOI:10.16189/j.nygc.2026.02.012

基于热路解析模型的山区光伏电站直埋电缆载流量计算及影响因素分析

Calculation of ampacity of directly buried cables in mountainous photovoltaic power plants based on thermal circuit model and analysis of influencing factors

谢伟东 1肖钢 1马自伟2

作者信息

  • 1. 中国电建集团华东勘测设计研究院有限公司,浙江 杭州 310030
  • 2. 云南农业大学,云南 昆明 650201
  • 折叠

摘要

Abstract

Direct-buried cables are often used as collection lines in photovoltaic power plants to collect and transport electrical energy.Accurate assessment of cable ampacity is the basis for cable selection in the design of photovoltaic power plants.This paper analyses the effects of soil moisture content,cable burial depth and soil boundary temperature on the YJLV22-26/35-3×400 three-core cable's ampacity according to the IEC 60287 thermal circuit analysis model,and proposes an approximate estimation formula for ampacity calculations.The study shows that reduced soil moisture content,increased cable burial depths and increased soil surface temperatures all decrease cable ampacity.Based on the conclusions of the study,measures to improve the ampacity of cables are proposed.

关键词

直埋电缆/载流量/热路模型

Key words

direct-buried cable/ampacity/thermal circuit model

分类

信息技术与安全科学

引用本文复制引用

谢伟东,肖钢,马自伟..基于热路解析模型的山区光伏电站直埋电缆载流量计算及影响因素分析[J].能源工程,2026,46(2):82-86,5.

能源工程

1004-3950

访问量0
|
下载量0
段落导航相关论文