基于自适应虚拟阻抗的构网型集中式储能变流器功率分配控制策略

Power Distribution Control Strategy of Grid-Forming Centralized Energy Storage Converter Based on Adaptive Virtual Impedance

王天宇 1范李平 2倪子华 2张子坤 1马辉1

作者信息

  • 1. 三峡大学 电气与新能源学院,湖北 宜昌 443002
  • 2. 国网湖北省电力有限公司宜昌供电公司,湖北 宜昌 443000
  • 折叠

摘要

Abstract

[Objective]Under the development background of high-proportion renewable energy integration driven by the"dual carbon"goals,the parallel operation of grid-forming energy storage converter(GFESC)has become the core solution for large-scale energy storage power stations.However,the inability to accurately allocate reactive power proportionally due to line impedance mismatch in parallel operation has emerged as a critical issue that urgently needs to be addressed.[Methods]The power transmission mechanism of the parallel converter system and the generation mechanism of reactive power allocation errors were first analyzed in depth through theoretical derivation.Based on this,an improved droop control strategy based on adaptive virtual impedance was proposed,aiming to dynamically compensate for the impact of line impedance mismatch on reactive power allocation.Finally,a parallel converter system model was built based on the Matlab/Simulink simulation platform,and the effectiveness of the proposed control strategy was verified through comparative experiments.[Results]The simulation results demonstrated that the proposed reactive power allocation strategy achieved high-precision proportional distribution under conditions where the actual line impedance was unknown and no inter-converter communication was required,while effectively reducing the output voltage deviation of the converters.After the introduction of virtual impedance,the strategy significantly mitigated the conflict between high-precision reactive power allocation and point of common coupling(PCC)voltage drop observed in conventional methods,enabling effective PCC voltage compensation to restore it to the rated operating level.Meanwhile,a double closed-loop control structure consisting of an outer voltage loop and an inner current loop is adopted to effectively maintain the stability of the system's grid voltage and frequency.[Conclusion]The strategy achieves precise matching of equivalent impedance through adaptive virtual impedance,providing a highly reliable solution for the large-scale operation of GFESC.

关键词

构网型储能变流器/并联变流器/自适应虚拟阻抗/无功功率分配

Key words

grid-forming energy storage converter/parallel converter/adaptive virtual impedance/reactive power allocation

分类

信息技术与安全科学

引用本文复制引用

王天宇,范李平,倪子华,张子坤,马辉..基于自适应虚拟阻抗的构网型集中式储能变流器功率分配控制策略[J].电机与控制应用,2026,53(6):580-591,12.

基金项目

国家自然科学基金(52377191) (52377191)

湖北省自然科学基金(2024AFB584)National Natural Science Foundation of China(52377191) (2024AFB584)

Natural Science Foundation of Hubei Province,China(2024AFB584) (2024AFB584)

电机与控制应用

1673-6540

访问量0
|
下载量0
段落导航相关论文