| 注册
首页|期刊导航|煤气与热力|水相变能与空气源双热源耦合热泵供暖实验

水相变能与空气源双热源耦合热泵供暖实验

王森 张昌建 罗景辉 平天祎 姜钊乐

煤气与热力2026,Vol.46Issue(8):11-16,6.
✕
煤气与热力2026,Vol.46Issue(8):11-16,6.

水相变能与空气源双热源耦合热泵供暖实验

Experimental Study on Coupled Heat Pump Heating System with Water Phase-Change Energy and Air-Source Dual Heat Sources

王森 1张昌建 2罗景辉 1平天祎 1姜钊乐1

作者信息

  • 1. 河北工程大学能源与环境工程学院,河北邯郸 056038||河北省暖通空调工程技术创新中心,河北邯郸 056038
  • 2. 河北工程大学能源与环境工程学院,河北邯郸 056038
  • 折叠

摘要

Abstract

A coupled heat pump heating system with water phase-change energy and air-source dual heat sources was designed,and three heat extraction meth-ods of the heat extraction unit were analyzed.Taking an office building as the heating target,experimental methods were employed to test and analyze indoor tem-perature and heat pump unit heating performance coef-ficient under the three heat extraction methods.Method A:The shell-type phase-change heat exchanger operates independently.Method B:The finned-tube air-cooled heat exchanger operates inde-pendently.Method C:The shell-type phase-change heat exchanger and finned-tube air-cooled heat exchanger operate in a coupled manner.When the out-door temperature ranges from-6 to-1 ℃,Method B fails to meet the minimum indoor temperature require-ments,while Methods A and C satisfies the minimum indoor temperature requirements.Compared with Method A,Method C presents a slightly lower average indoor temperature but a higher average heating COP of the heat pump unit.For Method B,the outdoor tem-perature exerts a significant impact on the performance of the heat pump unit,and the unit still fails to meet the minimum indoor temperature demand at an outdoor temperature of-6 to-1 ℃.When the outdoor tempera-ture is relatively low,Methods A and C are recom-mended for adoption.When assessing the operation performance of the heat pump unit,it is not feasible to rely solely on the heating COP,and the indoor tempera-ture should also be taken into full account.

关键词

双热源耦合热泵/水相变能/取热方式/制热性能系数

Key words

dual-source coupled heat pump/water phase-change energy/heat extraction method/heating performance coefficient

分类

建筑与水利

引用本文复制引用

王森,张昌建,罗景辉,平天祎,姜钊乐..水相变能与空气源双热源耦合热泵供暖实验[J].煤气与热力,2026,46(8):11-16,6.

基金项目

中央引导地方科技发展资助项目(236Z4310G) (236Z4310G)

煤气与热力

1000-4416

访问量0
|
下载量0
段落导航相关论文