制冷2026,Vol.45Issue(4):10-16,7.DOI:10.3969/J.ISSN.1005-9180.2026.04.0003
广州市某数据中心空调系统节能改造案例分析
Case Study of Energy Efficiency Retrofit for the HVAC System of a Data Center in Guangzhou
林敏聪1
作者信息
- 1. 广东省建科建筑设计院有限公司,广州,510013
- 折叠
摘要
Abstract
To address the challenges of ensuring business continuity and managing limited space during the retrofitting of existing data center air conditioning systems,this paper presents a case study of a retrofitting project in a Guangzhou data center.This case study meets these requirements without affecting the normal operation of non-retrofit areas.The implementation involves first constructing a backup cooling system to meet the air conditioning demands of IT equipment during the renovation.Once this system is stably operational,a new high-temperature chilled water system is constructed.Calculations indicate that the retrofitted data center zone achieves an annual PUE of 1.3 or less,representing a 12.7%reduction compared to the pre-retrofit system.Furthermore,given 1,580 annual hours with an outdoor air wet-bulb temperature at or below 13° C,the implementation of natural cooling via a plate heat exchanger lowers the annual PUE by approximately 1%relative to the scenario without natural cooling.关键词
数据中心/保障冷源系统/高温冷水/PUE/自然冷却Key words
Data Center/Cooling System Assurance/High-temperature Chilled Water/Power Usage Effectiveness/Free Cooling分类
建筑与水利引用本文复制引用
林敏聪..广州市某数据中心空调系统节能改造案例分析[J].制冷,2026,45(4):10-16,7.