郑州轻工业学院学报(自然科学版)2011,Vol.26Issue(5):5-7,3.
静态加热式空气源热泵热水器运行性能的试验研究
Experimental study of operating performance on static air-source heat pump water heater
王朝鑫 1朱兴旺 2邢林芬 1覃志成1
作者信息
- 1. 郑州轻工业学院机电工程学院,河南郑州450002
- 2. 广州中宇冷气科技发展有限公司,广东广州510935
- 折叠
摘要
Abstract
The operating performance of air heat pump water heater with static heating was tested based on air conditioning measurement platform. At ambient temperature of ( 20 ± 1) X with water tank temperature from 15 X to 55 X, the system parameters such as suction pressure and suction temperature had no significant change. Discharge pressure, discharge temperature, compression ratio and compressor input power all rose. The average COP was about 4. 76, and the system showed feasibility in energy saving.关键词
空气源热泵热水器/静态加热/系统平均性能系数Key words
air-source heat pump water heater/static heating/COP分类
通用工业技术引用本文复制引用
王朝鑫,朱兴旺,邢林芬,覃志成..静态加热式空气源热泵热水器运行性能的试验研究[J].郑州轻工业学院学报(自然科学版),2011,26(5):5-7,3.