首页|期刊导航|高压电器|800kV罐式断路器液压机构渗油的分析及对策

800kV罐式断路器液压机构渗油的分析及对策OA北大核心CSCDCSTPCD

Analysis and Countermeasures to Oil Leakage Fault of 800 kV Pot Breakers Hydraulic Mechanism

中文摘要英文摘要

结合一起800 kV罐式断路器液压机构渗油缺陷,认真分析机构组装工艺,并对机构零部件进行了检查测试,发现连接套设计公差偏大、现场安装方法不当是引发缺陷的根本原因.通过重新设计加工连接套、改进现场安装方法,彻底消除了机构存在的安全隐患,为后续800 kV罐式断路器安全运行奠定了基础.

Combined with the 800 kV pot breaker hydraulic mechanism oil seepage fault, the earnest analysis hydraulic mechanism assembles a craft, carried on a check test to hydraulic mechanism spare parts, discover conjunction parts tolerance bigger and installing method inaccuracy is the root reason that cause failures. Pass to re-design the conjunction parts and improvement to install a method, complete elimination the security risk exists for follow-up to 800 kV po…查看全部>>

李海波;万荣兴

甘肃省电力公司兰州输变电运行公司,兰州730050甘肃省电力公司兰州输变电运行公司,兰州730050

信息技术与安全科学

罐式断路器液压机构渗油

pot breaker hydraulic mechanism oil seepage fault

《高压电器》 2012 (9)

104-107,4